Violation Detail
Standard Cited: 19100335 A01 I Safeguards for personnel protection.
Inspection Nr: 1177124.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,224.00
Current Penalty: $9,540.40
Issuance Date: 11/28/2016
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 08/12/2017
Gravity: 10
Report ID: 0728500
Contest Date: 12/21/2016
Final Order: 05/12/2017
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 05/12/2017 | $9,540.40 | 08/12/2017 | Serious | |
Penalty | C: Contested | 02/15/2017 | $11,224.00 | 12/22/2016 | Serious | |
Penalty | Z: Issued | 11/28/2016 | $11,224.00 | 12/22/2016 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: (a) On and before September 2, 2016, in the Electrical Vault Room of the Mill Basement, an employee was exposed to serious electrical hazards in that he did not use Personnel Electrical Protective Equipment that was appropriate for the protection of his hands, arms, face and body, while attempting to change out the electrical fuses on an Energized 480 Volt Electrical Panel. As a result, an Arc Flash occurred seriously injuring the employee. Abatement certification is required for this item; use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.