Violation Detail
Standard Cited: 19100303 B08 I General.
Inspection Nr: 1171238.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,149.00
Current Penalty: $8,149.00
Issuance Date: 02/10/2017
Nr Instances: 2
Nr Exposed: 20
Abatement Date: 03/09/2017
Gravity: 5
Report ID: 0522000
Contest Date:
Final Order: 03/08/2017
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 02/10/2017 | $8,149.00 | 03/09/2017 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(b)(8)(i): Electric equipment shall be firmly secured to the surface on which it is mounted. Note to paragraph (b)(8)(i) of this section: Wooden plugs driven into holes in masonry, concrete, plaster, or similar materials are not considered secure means of fastening electric equipment: (a) There were two 220-volt electrical panels sitting on the floor without being secured to a surface, one on the Make Coil Line and one of the Open Coil Line.