Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1147532.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,742.00
Current Penalty: $3,742.00
Issuance Date: 10/27/2016
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 11/23/2016
Gravity: 1
Report ID: 0213900
Contest Date: 11/16/2016
Final Order: 08/26/2021
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 08/26/2021 | $3,742.00 | 11/23/2016 | Serious | |
Penalty | C: Contested | 01/31/2017 | $3,742.00 | 11/23/2016 | Serious | |
Penalty | Z: Issued | 10/27/2016 | $3,742.00 | 11/23/2016 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected: a) Chemical storage area outside of compounding area: Toluene and naptha, category 2 flammable liquids, were transferred from 55 gallon drums without the nozzle of the pump being electrically connected to the transfer container, on or about 5/16/16. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.