Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1131939.015
Citation: 01004
Citation Type: Other
Abatement Status: Quick Fix
Initial Penalty: $6,436.00
Current Penalty: $6,000.00
Issuance Date: 09/01/2016
Nr Instances: 1
Nr Exposed: 100
Abatement Date:
Gravity:
Report ID: 0418600
Contest Date:
Final Order: 09/13/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/13/2016 | $6,000.00 | Other | ||
Penalty | Z: Issued | 09/01/2016 | $6,436.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP): a) Engine Room (Processing Plant); On or about March 9, 2016 and at times prior;, the employer did not ensure that the exit doors opening to the outside of the engine room were tight fitting doors as specified in IIAR 2-2008 Standard Section 13 (Machinery Room Design) which states each refrigerating machinery room shall have a tight-fitting door or doors opening outward.