Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
Inspection Nr: 1127562.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,500.00
Current Penalty: $2,450.00
Issuance Date: 08/01/2016
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 08/25/2016
Gravity: 5
Report ID: 0213900
Contest Date: 10/14/2016
Final Order: 11/27/2017
Related Event Code (REC):
Emphasis:
Failure to Abate | |||||||
---|---|---|---|---|---|---|---|
Activity Nr | Issuance | Penalty | Contest | Final Order | |||
1180944 | 11/07/2016 | $9,750.00 | 12/01/2016 |
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 05/09/2019 | $3,500.00 | 08/25/2016 | Serious | |
Penalty | J: ALJ Decision | 11/27/2017 | $2,450.00 | 08/25/2016 | Serious | |
FTA | I: Informal Settlement | 12/01/2016 | $9,750.00 | 11/15/2016 | 1180944.015 | |
FTA | Z: Issued | 11/07/2016 | $15,000.00 | 11/15/2016 | 1180944.015 | |
Penalty | Z: Issued | 08/01/2016 | $3,500.00 | 08/25/2016 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." a) Facility: Square D Circuit breakers used to turn the lights on and off in the facility were not listed and marked with SWD, on or about 2/24/2016. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.