Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1017331.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,850.00
Current Penalty: $2,695.00
Issuance Date: 07/01/2015
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 07/07/2015
Gravity: 5
Report ID: 0214500
Contest Date: 07/23/2015
Final Order: 06/06/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 06/06/2016 | $2,695.00 | 07/07/2015 | Serious | |
| Penalty | C: Contested | 07/24/2015 | $3,850.00 | 07/07/2015 | Serious | |
| Penalty | Z: Issued | 07/01/2015 | $3,850.00 | 07/07/2015 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Wood Shop: An air heater classified as "Household Use Only" used to provide thermal comfort for employees, was located in an area where a potential breach of wood processing equipment and a Grizzly enclosureless dust collector, were present. Wood working equipment generates combustible dust classified as a Class II explosive dust, and presents a potential fire hazard, on or about, 2/15/15.