Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1012612.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,900.00
Current Penalty: $2,940.00
Issuance Date: 05/06/2015
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 05/18/2015
Gravity: 10
Report ID: 0524530
Contest Date:
Final Order: 06/01/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/01/2015 | $2,940.00 | 05/18/2015 | Serious | |
Penalty | Z: Issued | 05/06/2015 | $4,900.00 | 05/18/2015 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: In the spray painting area, a 120V AC electrical receptacle was observed covered with combustible residues and was not classified for the hazardous location.