Violation Detail
Standard Cited: 19100137 B02 VIII Electrical protective equipment.
Inspection Nr: 1011105.015
Citation: 01004
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $2,550.00
Current Penalty: $1,275.00
Issuance Date: 05/15/2015
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 1
Report ID: 0215800
Contest Date: 06/09/2015
Final Order: 08/31/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 08/31/2015 | $1,275.00 | Serious | ||
Penalty | C: Contested | 06/19/2015 | $2,550.00 | Serious | ||
Penalty | Z: Issued | 05/15/2015 | $2,550.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6: a) Maintenance Shop, on or about 12/5/14: High voltage rubber insulating gloves were not subjected to testing every six months.