Violation Detail
Standard Cited: 19100165 B02 Employee alarm systems.
Inspection Nr: 191250.015
Citation: 01003D
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/07/2012
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 08/28/2012
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 08/27/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/27/2012 | $0.00 | 08/28/2012 | Serious | |
| Penalty | Z: Issued | 08/07/2012 | $0.00 | 08/28/2012 | Serious |
Text For Citation: 01 Item/Group: 003D Hazard:
29 CFR 1910.165(b)(2): The employee alarm could not be perceived above ambient noise or light levels by all employees in the affected portions of the workplace: a) Boiler Room - There was no audible or visual alarm to warn of a release of anhydrous ammonia outside of the entrance to the ammonia room. On or about 2/8/12. Abatement note 1: ASHRAE 15 2010, 8.11.2.1 requires that the alarm shall annunciate visual and audible alarms inside the refrigerating machinery room and outside each entrance to the refrigerating machinery room. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.