Violation Detail
Standard Cited: 19100119 E03 III Process safety management of highly hazardous chemicals.
Inspection Nr: 329260.015
Citation: 01003C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $0.00
Issuance Date: 09/18/2012
Nr Instances: 13
Nr Exposed: 78
Abatement Date: 10/02/2012
Gravity: 10
Report ID: 0625700
Contest Date:
Final Order: 10/08/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/08/2012 | $0.00 | 10/02/2012 | Serious | |
| Penalty | Z: Issued | 09/18/2012 | $7,000.00 | 10/02/2012 | Serious |
Text For Citation: 01 Item/Group: 003C Hazard:
29 CFR 1910.119(e)(3)(iii): The process hazard analysis (PHA) did not address the engineering and administrative controls applicable to the hazards and their interrelationship(s): Instance 1 In Area 1 of the VCM unit: The employer did not adequately address the engineering and administrative controls applicable to the hazards of the process in the 2009 PHA by failing to recognize and evaluate the lack of appropriate safeguards to ensure that the following pressure relief devices (PRDs) did not have their relief capabilities diminished or eradicated by intervening stop valves: 1. PSV-E7101A-D, PSE-E7101A-C; 2. PSV-E7104A; 3. PSV-E7106A; 4. PSV-T7103A-B, PSE- T7103A-B; 5. PSV-V7108A-A, PSE-V7108A-A; 6. PSV-V7108A-B, PSE-V7108A-B; 7. PSV-E7102B-C, PSE-E7102B-C; 8. PSE-V7105A-A, PSE-V7105A-B; 9. PSE-V7106A-A, PSE-V7106A-B. Instance 2 In Areas 1, 2, and 3 of the VCM unit: The employer did not adequately address the engineering controls applicable to the hazards of the process by failing to ensure that the following pressure relief valves (PRVs) provided sufficient relief for the equipment they protected prior to listing them as safeguards on the 2009 PHA: 1. PSV-T7103A-B; 2. PSV-E7313-B; 3. PSV-E7213A-A; 4. PSV-E7213A-B.
Translate