Standard Cited: 19100333 B02 IV B Selection and use of work practices
Inspection Nr: 1806333.015
Citation: 01003C
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/21/2025
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 10/09/2025
Gravity: 10
Report ID: 0214200
Contest Date: 09/17/2025
Final Order:
Related Event Code (REC): A;R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | C: Contested | 09/18/2025 | $0.00 | 10/09/2025 | Serious | |
| Penalty | Z: Issued | 08/21/2025 | $0.00 | 10/09/2025 | Serious |
Text For Citation: 01 Item/Group: 003C Hazard:
29 CFR 1910.333(b)(2)(iv)(B): The test of the circuit elements and electrical parts of equipment did not determine if any energized condition existed as a result of inadvertently induced voltage or unrelated voltage backfeed: Location: 60 Earhart Drive. Newark, NJ 07114 - Rail Link SOP 11-12 a: The employer failed ensure procedures were developed to verify electrical parts could not become energized from voltage backfeed caused by rail cars moving through the rail crossover. Employees were exposed to electrocution hazards while replacing fuses in an electrical panel after such panel became re-energized as a train was towed through the crossover. Violation occurred on or about February 25, 2025.