Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1794730.015
Citation: 01003C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/17/2025
Nr Instances: 2
Nr Exposed: 33
Abatement Date: 07/15/2025
Gravity: 10
Report ID: 0626300
Contest Date:
Final Order: 07/24/2025
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/24/2025 | $0.00 | 07/15/2025 | Serious | |
Penalty | Z: Issued | 06/17/2025 | $0.00 | 07/15/2025 | Serious |
Text For Citation: 01 Item/Group: 003C Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) On or about December 19, 2024, and at times prior to, in the welding area, where circuit breaker panels were not marked to indicate the purpose of individual breakers. b) On or about December 19, 2024, and at times prior to, in the managers office, where circuit breaker panels were not marked to indicate the purpose of individual breakers.