Violation Detail
Standard Cited: 19100119 E03 V Process safety management of highly hazardous chemicals.
Inspection Nr: 994383.015
Citation: 01003B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/06/2015
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 07/01/2015
Gravity:
Report ID: 0524200
Contest Date:
Final Order: 03/27/2015
Related Event Code (REC):
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/27/2015 | $0.00 | 07/01/2015 | Other | |
Penalty | Z: Issued | 03/06/2015 | $0.00 | 05/13/2015 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.119(e)(3)(v): The process safety hazard analyses did not address facility siting. a) Hi Temp Northlake LLC. dba Bluewater Thermal Solutions - The employer's January 13, 2011 and April 30, 2014 process hazard analyses (PHA) did not address for the process of ammonia dissociaton the facility siting, which include, but are not limited to: 1) The spacing between components in the furnace area. 2) The location of large inventories of ammonia in the outside storage area. 3) The location of furnaces, weld shops, forklift traffic and other likely sources of ignition. 4) The location of the truck dock in relation to the ammonia storage tanks. 5) The electrical classification of the facility.