Violation Detail
Standard Cited: 19100333 B02 Selection and use of work practices
Inspection Nr: 980882.015
Citation: 01003B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/10/2014
Nr Instances: 2
Nr Exposed: 1
Abatement Date: 01/02/2015
Gravity: 10
Report ID: 0936200
Contest Date:
Final Order: 01/05/2015
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 12/10/2014 | $0.00 | 01/02/2015 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were de-energized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): On or about 13 June 2014 At Naval Base Ventura, Point Mugu, an employee working on the de-energized low side of a 150KVA 4160-120/208V 3 Phase delta/wye dry pack transformer, reached in through the high voltage side which had not been locked out resulting in employee being electrocuted.