Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 494598.015
Citation: 01003B
Citation Type: Serious
Abatement Date: 01/03/2013 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/20/2012
Nr Instances: 1
Nr Exposed: 30
Related Event Code (REC):
Gravity: 5
Report ID: 0316400
Contest Date:
Final Order: 01/14/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/14/2013 | $0.00 | 01/03/2013 | Serious | |
Penalty | Z: Issued | 12/20/2012 | $0.00 | 01/03/2013 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: (a) Dye Production and Distillation Areas: Dayton Electric Chain Hoists were used at the process reactors to lift containers of flammable liquids onto the work deck and they were not electrically approved for a Class I Division 2 area where large quantities of flammable liquids were present in process reactors as determined on July 18, 2012. ABATEMENT CERTIFICATION IS REQUIRED.