Violation Detail
Standard Cited: 19100119 E03 IV Process safety management of highly hazardous chemicals.
Inspection Nr: 315026617
Citation: 01003B
Citation Type: Other
Abatement Status: X
Initial Penalty:
Current Penalty:
Issuance Date: 04/18/2011
Nr Instances: 4
Nr Exposed: 10
Abatement Date: 05/12/2011
Gravity: 10
Report ID: 1032500
Contest Date: 05/09/2011
Final Order: 03/14/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 03/14/2012 | 05/12/2011 | Other | ||
| Penalty | Z: Issued | 04/18/2011 | 05/12/2011 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard: CHEMNEP
29 CFR 1910.119(e)(3)(iv): The process hazard analysis (PHA) did not address the consequences of failure of engineering and administrative controls. (a) On or about November 29, 2010, and at times prior thereto, the 2009 PHA did not address the potential impact of a natural gas leak to the site ammonia system. (b) On or about November 29, 2010, the 2009 PHA did not address the potential impact of adverse weather to the site ammonia system. (c) On or about November 29, 2010, the 2009 PHA did not address the potential impact of a power failure to the site ammonia system. (d) On or about November 29, 2010, the 2009 PHA did not address the potential impact of a severed charging line while filling the high pressure receiver. Note: Abatement certification and documentation ARE required for this item.
Translate