Violation Detail
Standard Cited: 19100119 E03 V Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 312487457
Citation: 01003B
Citation Type: Serious
Abatement Status:
Initial Penalty:
Current Penalty:
Issuance Date: 07/08/2009
Nr Instances: 1
Nr Exposed: 8
Abatement Date: 08/10/2009
Gravity: 10
Report ID: 0317000
Contest Date: 07/28/2009
Final Order: 01/17/2012
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/17/2012 | 08/10/2009 | Serious | ||
Penalty | Z: Issued | 07/08/2009 | 08/10/2009 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard: REFINERY
29 CFR 1910.119(e)(3)(v): The process hazard analysis did not address facility siting: a) Sunoco, Inc. Marcus Hook Refinery, 12-4 LSG Unit - The 2003 PHA conducted for the Low Sulfur Gasoline (LSG) Project did not address the facility siting of the LSG unit operator shelter/control room. The structure was determined by the employer to be occupied, and the area where the structure was located was determined by the employer to be potentially exposed to an overpressure in excess of one (1) pounds per square inch (psi) in the event of a vapor cloud explosion. Condition noted on or about 03/30/2009. NOTE: DOCUMENTATION OF ABATEMENT OF THIS CONDITION IS REQUIRED Abatement Note OSHA does not accept occupancy criteria evaluations (see API 752, Section 2.5.2) as the basis for an employer's determination that adequate protection has been provided for employees in occupied structures which employer's have identified as being potentially subject to explosions, fire, ingress of toxic materials or high energy releases.