Violation Detail
Standard Cited: 19100147 C04 II The control of hazardous energy (lockout/tagout).
Inspection Nr: 1843132.015
Citation: 01003B
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/09/2026
Nr Instances: 1
Nr Exposed: 14
Abatement Date: 02/20/2026
Gravity: 10
Report ID: 0317500
Contest Date: 02/27/2026
Final Order:
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | C: Contested | 02/27/2026 | $0.00 | 02/20/2026 | Serious | |
| Penalty | Z: Issued | 02/09/2026 | $0.00 | 02/20/2026 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D): a) In the 13, 14 Battery Transfer Area Pad Valve Pit, on or about August 11, 2025 - The employer's procedures for the control of hazardous energy did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be used to control chemical energy when employees cleaned the seat of 13 Pad Valve with water when cryogenically-processed coke oven gas was present in the valve and Underfire lines. This exposed employees washing the valve, as well as other employees working in or adjacent to the 13, 14 Battery Transfer Area to an explosion when 13 Pad Valve ruptured during washing and released cryogenically-processed coke oven gas from the Underfire lines.
Translate