Violation Detail
Standard Cited: 19100307 C03 Hazardous (classified) locations.
Inspection Nr: 1508322.015
Citation: 01003B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $13,653.00
Current Penalty: $0.00
Issuance Date: 06/21/2021
Nr Instances: 1
Nr Exposed: 11
Abatement Date: 08/17/2023
Gravity: 10
Report ID: 0728500
Contest Date: 07/16/2021
Final Order: 03/06/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/06/2023 | $0.00 | 08/17/2023 | Other | |
Penalty | C: Contested | 07/19/2021 | $13,653.00 | 07/16/2021 | Serious | |
Penalty | Z: Issued | 06/21/2021 | $13,653.00 | 07/16/2021 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.307(c)(3):The equipment used in the hazardous(classified) location was not of the type and design that would provide protection from the hazards arising from the combustibility and flammability of vapors, liquids, gases, dusts, or other fibers involved. The employer is failing to protect employees from fire and explosion hazards. This was most most recently documented on December 31, 2020, at the worksite located at 438 County Road 11002, Adrian, Missouri. The employer had a heater replaced in the elevator office approximately sixty days prior to December 31, 2020. The employer installed a heater that did not have a Class II dust proof/tight rating for use in the facility where Class II Division 2 electrical is required.