Violation Detail
Standard Cited: 19100269 L08 V D Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1445072.015
Citation: 01003B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/10/2020
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 02/19/2020
Gravity: 5
Report ID: 0419400
Contest Date:
Final Order: 03/27/2020
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/27/2020 | $0.00 | 02/19/2020 | Serious | |
| Penalty | Z: Issued | 02/10/2020 | $0.00 | 02/19/2020 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.269(l)(8)(v)(D): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective equipment consisting of at a minimum a face shield with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2 but less than 9.0 Cal/cm2: (a) A.H. McCoy Federal Building Electrical Vault - On or about November 13, 2109 employee assisting in the performance of a phase test was exposed to arc flash burn hazard. Employee was not wearing an arc rated face shield.