Violation Detail
Standard Cited: 19100333 B02 IV B Selection and use of work practices
Inspection Nr: 1315548.015
Citation: 01003B
Citation Type: Serious
Abatement Date: 11/30/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/02/2018
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): A
Gravity: 10
Report ID: 0418100
Contest Date:
Final Order: 11/28/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/28/2018 | $0.00 | 11/30/2018 | Serious | |
Penalty | Z: Issued | 11/02/2018 | $0.00 | 11/30/2018 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts were deenergized: On or about May 3, 2018 at 3936 LaVista Road, Tucker, Georgia after replacing the ballast and prior to replacing lamps in the sign, a qualified person did not use testing equipment to verify that the wall mounted disconnect actually deenergized the sign.