Violation Detail
Standard Cited: 19100119 E03 V Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1269114.015
Citation: 01003B
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/06/2018
Nr Instances: 1
Nr Exposed: 7
Abatement Date: 05/02/2018
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 04/30/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/30/2018 | $0.00 | 05/02/2018 | Serious | |
Penalty | Z: Issued | 04/06/2018 | $0.00 | 05/02/2018 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.119(e)(3)(v): The PHA did not address facility siting: a) GEA/FES and Frick ammonia refrigeration systems: The PHA was inadequate in addressing facility siting hazards. The PHA did not address a means of egress from the roof for employees conducting maintenance. In the event of an emergency, employees would have to re-enter the building, potentially through a hazardous area, in order to evacuate from the roof, on or about 10/11/2016. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.