Violation Detail
Standard Cited: 19100303 G02 II General.
Inspection Nr: 1261379.015
Citation: 01003B
Citation Type: Serious
Abatement Status: Not Completed - Worksite Changed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/09/2018
Nr Instances: 3
Nr Exposed: 15
Abatement Date: 01/18/2018
Gravity: 10
Report ID: 0830600
Contest Date:
Final Order: 02/07/2018
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 01/09/2018 | $0.00 | 01/18/2018 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage: a) Main Shop Near West Exit: On or about August 30, 2017, and at times prior, workers were exposed to electrical hazards where a fluorescent light fixture positioned 87 inches (7ft 3in) from the floor was not protected from damage that would result in exposure to live electrical parts. b) Main Shop Wash Room: On or about August 30, 2017, and at times prior, workers were exposed to electrical hazards where a fluorescent light fixture positioned 91 inches (7ft 7in) from the floor was not protected from damage that would result in exposure to live electrical parts. c) Back Shop: On or about August 30, 2017, and at times prior, workers were exposed to electrical hazards where a fluorescent light fixture positioned 74.5 inches (6ft 2.5in) from the floor was not protected from damage that would result in exposure to live electrical parts. Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).