Violation Detail
Standard Cited: 19100106 B04 III Flammable liquids.
Inspection Nr: 1077446.015
Citation: 01003B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/19/2016
Nr Instances: 2
Nr Exposed: 4
Abatement Date: 07/13/2016
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 02/05/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/05/2016 | $0.00 | 07/13/2016 | Serious | |
Penalty | Z: Issued | 01/19/2016 | $0.00 | 07/13/2016 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.106(b)(4)(iii): Vent piping was not constructed in accordance with paragraph (c) of this section: A. On or about July 20, 2015, Flammable Area: Vent piping for the tanks of acetone and isopropyl alcohol 99% was not constructed of steel, nodular iron or malleable iron. The vent piping for tanks 5T38 Green and 5T37 Blue was made of PVC, which can distort at 90 degrees C / 194 degrees F.