Violation Detail
Standard Cited: 19100106 D04 I Flammable liquids.
Inspection Nr: 934163.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,900.00
Current Penalty: $2,500.00
Issuance Date: 11/20/2013
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 12/13/2013
Gravity: 10
Report ID: 0830100
Contest Date:
Final Order: 12/09/2013
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/09/2013 | $2,500.00 | 12/13/2013 | Serious | |
Penalty | Z: Issued | 11/20/2013 | $4,900.00 | 12/13/2013 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.106(d)(4)(i): Opening(s) from inside flammable and combustible storage room(s) into other rooms or buildings were not provided with noncombustible liquid tight raised seal or ramp at least 4 inches in height: a) Distillation Room; On or about August 19, 2013 and at times prior, employees were exposed to fire and explosion hazards when flammable liquids such as but not limited to; Methyl alcohol, (Lacquer Thinners and Cleaning Solvents 105); Butyl Acetate, (Chroma Premier System 14385S and Chroma Premier Pro 74500S) were stored in a room that would not contain these flammable liquids in the event of a spill.