Violation Detail
Standard Cited: 19100119 E03 I Process safety management of highly hazardous chemicals.
Inspection Nr: 311796635
Citation: 01003A
Citation Type: Serious
Abatement Status: X
Initial Penalty: $5,000.00
Current Penalty: $2,500.00
Issuance Date: 06/08/2010
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 07/23/2010
Gravity: 10
Report ID: 0112000
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/24/2010 | $2,500.00 | 07/23/2010 | Serious | |
| Penalty | Z: Issued | 06/08/2010 | $5,000.00 | 07/23/2010 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard: CHEMNEP
29 CFR 1910.119(e)(3)(i): The process hazard analysis did not address the hazards of the process: Company: The Process Hazard Analysis conducted by the company of the ammonia refrigeration system did not address hazards associated with purging equipment of ammonia prior to opening piping and equipment. Employees routinely purged ammonia from piping and equipment using a hose and barrel of water, sometimes setting off the ammonia sensor in the mechanical room. Specific Abatement Documentation is Required