Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1802527.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $4,522.00
Current Penalty: $3,000.00
Issuance Date: 03/27/2025
Nr Instances: 1
Nr Exposed: 1
Abatement Date:
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 04/17/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 04/17/2025 | $3,000.00 | Serious | ||
| Penalty | Z: Issued | 03/27/2025 | $4,522.00 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Forklift charging area: On, or about, February 5, 2025, a metal floor bumper was installed in the working space of the 460 volt Generac generator enclosure.
Translate