Violation Detail
Standard Cited: 19100107 B05 I Spray finishing using flammable and combustible materials.
Inspection Nr: 1592595.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,360.00
Current Penalty: $10,360.00
Issuance Date: 06/16/2022
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 05/01/2023
Gravity: 5
Report ID: 0626600
Contest Date:
Final Order: 07/13/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 02/17/2023 | $10,360.00 | 05/01/2023 | Serious | |
Penalty | P: Petition to Mod Abatement | 01/09/2023 | $10,360.00 | 02/15/2023 | Serious | |
Penalty | P: Petition to Mod Abatement | 11/17/2022 | $10,360.00 | 12/30/2022 | Serious | |
Penalty | P: Petition to Mod Abatement | 09/28/2022 | $10,360.00 | 11/17/2022 | Serious | |
Penalty | I: Informal Settlement | 07/13/2022 | $10,360.00 | 10/03/2022 | Serious | |
Penalty | Z: Issued | 06/16/2022 | $10,360.00 | 08/04/2022 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.107(b)(5)(i):The average air speed over the open face of the paint spray booth was less than 100 linear feet per minute and there were no visible gauges, audible alarms or pressure activated devices installed in paint spray booth to indicate or ensure that the required air speed was maintained: On or about April 29, 2022, an employee was exposed to a fire hazard while painting valves in a spray booth that did not have visible gauges, alarms, or pressure activated devices and did not have an air speed over 100 linear feet per minute.