Violation Detail
Standard Cited: 19100303 G01 II General.
Inspection Nr: 1562253.015
Citation: 01003A
Citation Type: Serious
Abatement Date: 01/31/2022 2
Initial Penalty: $5,851.00
Current Penalty: $4,681.20
Issuance Date: 12/17/2021
Nr Instances: 2
Nr Exposed: 20
Related Event Code (REC):
Gravity: 1
Report ID: 0936200
Contest Date:
Final Order: 12/30/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/30/2021 | $4,681.20 | 01/31/2022 | Serious | |
Penalty | Z: Issued | 12/17/2021 | $5,851.00 | 01/14/2022 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: On or Before November 4, 2021, the employer permitted materials to be stored directly in front of the electrical panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition exposed employees to an electrical and/or fire hazard(s). In the follow locations: (a) IDF Room (b) Pump Room