Violation Detail
Standard Cited: 19100335 A01 I Safeguards for personnel protection.
Inspection Nr: 1518476.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,653.00
Current Penalty: $0.00
Issuance Date: 06/30/2021
Nr Instances: 1
Nr Exposed: 20
Abatement Date: 07/19/2021
Gravity: 10
Report ID: 0524700
Contest Date:
Final Order: 07/21/2021
Related Event Code (REC): A
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/21/2021 | $0.00 | 07/19/2021 | Serious | |
Penalty | Z: Issued | 06/30/2021 | $13,653.00 | 07/19/2021 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a.) On or about March 9, 2021, the employer did not ensure electricians were protected while performing work on or near 480V circuits. Employees were required to troubleshoot loose connections for the Galv Line electrical cabinet in the MCC Room and did not wear required hand and body protection while performing live electrical work, exposing them to electrical shock and arc flash hazards.