Violation Detail
Standard Cited: 19100269 L08 III Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1487317.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,398.00
Current Penalty: $3,238.80
Issuance Date: 10/19/2020
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 12/29/2020
Gravity: 10
Report ID: 0418400
Contest Date:
Final Order: 11/12/2020
Related Event Code (REC): C
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/12/2020 | $3,238.80 | 12/29/2020 | Serious | |
| Penalty | Z: Issued | 10/19/2020 | $5,398.00 | 12/29/2020 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.269(l)(8)(iii): The employer did not ensure that each employee who is exposed to hazards from flames or electric arcs does not wear clothing that could melt onto his or her skin or that could ignite and continue to burn when exposed to flames or the heat energy estimated under paragraph (l)(8)(ii) of this section: A) SOLAmerica Solar Farm, on or about August 6, 2020, the employer failed to take corrective action when an employee was working in 600 VAC disconnect boxes wearing an exterior shirt that was 50% polyester material, thereby exposing the employee to burns from an arc flash.