Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1466507.015
Citation: 01003A
Citation Type: Serious
Abatement Date: 10/19/2020 2
Initial Penalty: $6,747.00
Current Penalty: $2,800.00
Issuance Date: 08/31/2020
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): C
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 09/28/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/28/2020 | $2,800.00 | 10/19/2020 | Serious | |
Penalty | Z: Issued | 08/31/2020 | $6,747.00 | 10/19/2020 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: ADHESIVE SPRAY AREA: On or about and at times prior to March 12, 2020, electrical wiring and equipment including, but not limited to outlets, overhead lighting, a pinch roller, a lift, power tools, and a forklift, were used within 20 feet of the area where a Category 2 flammable adhesive was sprayed on boards to attach laminate as part of the cabinet manufacturing process. The electrical equipment was not approved for hazardous locations.