Violation Detail
Standard Cited: 19100304 G05 Wiring design and protection.
Inspection Nr: 1446937.015
Citation: 01003A
Citation Type: Serious
Abatement Date: 04/14/2020 2
Initial Penalty: $10,603.00
Current Penalty: $10,603.00
Issuance Date: 03/25/2020
Nr Instances: 3
Nr Exposed: 20
Related Event Code (REC):
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 04/20/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 03/25/2020 | $10,603.00 | 04/14/2020 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. a. On or about November 22, 2019, located outside the front of Press 201, there was a slitter table with an ITS (Innovative Tooling Solutions) electrical control box with a flexible cord plug end without a grounding pin, thereby exposing employees to fire and electrical shock hazards up to 120 VAC. b. On or about November 22, 2019, located behind Press 209, there was a floor fan supplied with an extension cord with a flexible cord plug end without a grounding pin, thereby exposing employees to fire and electrical shock hazards up to 120 VAC. c. On or about November 22, 2019, located at Press 217, there was a floor fan supplied with an extension cord with its cord plug end without a grounding pin, thereby exposing employees to fire and electrical shock hazards up to 120 VAC.