Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 1392711.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $9,282.00
Current Penalty: $9,282.00
Issuance Date: 09/20/2019
Nr Instances: 2
Nr Exposed: 60
Abatement Date: 09/30/2019
Gravity: 10
Report ID: 0522300
Contest Date:
Final Order: 10/09/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/09/2019 | $9,282.00 | 09/30/2019 | Serious | |
Penalty | Z: Issued | 09/20/2019 | $9,282.00 | 09/30/2019 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons: On or about April 19, 2019, the employer was storing and using approximately 220 gallons of flammable liquids including UN1263 Varnish outside of a storage room or cabinet in the Braiding Department. The employer was storing and using approximately 66 gallons of flammable liquids including Wire Marking Ink containing Toluene and Cyclohexane outside of a storage room or cabinet in the Braiding and Extruding Department. The employer was also storing and using approximately 110 gallons of flammable liquids including UN2920 solution outside of a storage room or cabinet in the Extruding Department.