Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1344108.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,543.00
Current Penalty: $3,325.80
Issuance Date: 09/19/2018
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 10/01/2018
Gravity: 1
Report ID: 0625400
Contest Date:
Final Order: 10/09/2018
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/09/2018 | $3,325.80 | 10/01/2018 | Serious | |
| Penalty | Z: Issued | 09/19/2018 | $5,543.00 | 10/01/2018 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about September 5, 2018, at the disconnect panel box labeled Gang Rip Saw, HC3, the breakers were not identified to indicate their purpose. Employees gain access to the disconnect box to isolate the energy sources for the Gang Rip Saw under the company's energy control program.