Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1213462.015
Citation: 01003A
Citation Type: Serious
Abatement Date: 09/07/2017 2
Initial Penalty: $9,959.00
Current Penalty: $6,000.00
Issuance Date: 08/09/2017
Nr Instances: 2
Nr Exposed: 6
Related Event Code (REC):
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 08/30/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/30/2017 | $6,000.00 | 09/07/2017 | Serious | |
Penalty | Z: Issued | 08/09/2017 | $9,959.00 | 09/07/2017 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.119(d)(3)(ii): The employer shall document that equipment complies with recognized and generally accepted good engineering practices. a) On or about March 7, 2017, there was not an eyewash/safety shower in the engine room as required by International Institute of Ammonia Refrigeration (IIAR) 2-2014 Section 6.7.1. b) On or about March 7, 2017, the oil pot PO4B01 was not provided with a self-closing valve as required by International Institute of Ammonia Refrigeration (IIAR) 2-2014 Section 5.9.3. c) On or about March 7, 2017, the .75 inch HTRS pipe section associated with Oil Pot OP4B01 was mislabeled HTRL. International Institute of Ammonia Refrigeration (IIAR) 2-2014 Section 5.14.5 requires ammonia piping being properly labeled. d) On or about March 7, 2017, several outdoor ammonia pipe section labeling was illegible or missing information. International Institute of Ammonia Refrigeration (IIAR) 2-2014 Section 5.14.5 requires ammonia piping being properly labeled. e) On or about March 7, 2017, Valve HV1A17, Ammonia Transfer Pump #1 PU4B04, Strainer STR6N02, Strainer STR 6N03, Valve FCV 6N03, Valve FCV 6B16 and Strainer STR 6B17 were missing identification tags. International Institute of Ammonia Refrigeration (IIAR) 2-2014 Section 5.14.2 requires refrigeration equipment to be labeled.