Violation Detail
Standard Cited: 19100305 E01 Wiring methods, components, and equipment for general use.
Inspection Nr: 1096479.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $3,500.00
Issuance Date: 03/24/2016
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 04/14/2016
Gravity: 10
Report ID: 0728100
Contest Date:
Final Order: 04/15/2016
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/15/2016 | $3,500.00 | 04/14/2016 | Serious | |
Penalty | Z: Issued | 03/24/2016 | $7,000.00 | 04/14/2016 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures (a) In the vestibule leading to the back door, a circuit breaker box used as a junction box was not installed to prevent moisture and/or water from entering the box. The box was exposed to water intrusion from the ceiling and when water that traveled down the wall to the box. This condition exposed workers to fire and electrical hazards.