Violation Detail
Standard Cited: 19100269 M03 II Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1078576.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,900.00
Current Penalty: $4,900.00
Issuance Date: 01/08/2016
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 04/29/2016
Gravity: 10
Report ID: 0830500
Contest Date: 01/29/2016
Final Order: 06/27/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 06/27/2016 | $4,900.00 | 04/29/2016 | Serious | |
| Penalty | C: Contested | 01/29/2016 | $4,900.00 | 02/03/2016 | Serious | |
| Penalty | Z: Issued | 01/08/2016 | $4,900.00 | 02/03/2016 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.269(m)(3)(ii): All switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized shall be open. Such means inoperable, unless its design does not so permit, and such means shall be tagged to indicate that employees are at work. (a) Morgan County Rural Electric Association at Washington County Roads 20 & E, Woodrow, CO 80757: On or before July 10, 2015, all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized were not open. The disconnect switches for Feeder 1 were located about a mile away and were not opened to deenergize the back feed to the South Woodrow Substation. On July 10, 2015 an employee was electrocuted when he came into contact with 7.2 kV, phase to ground. This condition exposed employees to electric shock and/or an electrocution hazard.