Violation Detail
Standard Cited: 19100106 B02 VI B Flammable liquids.
Inspection Nr: 1077446.015
Citation: 01003A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,500.00
Current Penalty: $2,100.00
Issuance Date: 01/19/2016
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 07/13/2016
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 02/05/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/05/2016 | $2,100.00 | 07/13/2016 | Serious | |
| Penalty | Z: Issued | 01/19/2016 | $3,500.00 | 07/13/2016 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.106(b)(2)(vi)(b): Where vent pipe outlets for tanks storing Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), are adjacent to buildings or public ways, they were not located so that the vapors are released at a safe point outside of buildings and not less than 12 feet above the adjacent ground level. In order to aid their dispersion, vapors were not discharged upward or horizontally away from closely adjacent walls. Vent outlets were not located so that flammable vapors were not trapped by eaves or other obstructions and shall be at least five feet from building openings: A. On or about July 20, 2015, east side of building outside flammable room: The vent pipe from acetone tank 5T38 Green was turned 180 degrees and vapors were discharged downward instead of upward or horizontally as required by this section.