Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100119 F01 IV Process safety management of highly hazardous chemicals.

Inspection Nr: 999145.015

Citation: 01003

Citation Type: Serious

Abatement Status: Abatement Completed

Initial Penalty: $7,000.00

Current Penalty: $3,500.00

Issuance Date: 02/05/2015

Nr Instances: 1

Nr Exposed: 1512

Abatement Date: 02/23/2015

Gravity: 10

Report ID: 0627700

Contest Date: 03/20/2015

Final Order: 05/18/2015

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty C: Contested 08/31/2015 $7,000.00 02/23/2015 Serious  
Penalty F: Formal Settlement 05/18/2015 $3,500.00 02/23/2015 Serious  
Penalty Z: Issued 02/05/2015 $7,000.00 02/23/2015 Serious  

Text For Citation: 01 Item/Group: 003 Hazard:

29 CFR 1910.119(f)(1)(iv): The employer does not ensure written procedures address the requirements for the safety systems and their functions. The violation occurred in the Main and GCS Ammonia Refrigeration Systems on or about October 8, 2014 and at times prior thereto. Employees were exposed to fire, explosion, and/or inhalation hazards from ammonia vapors when the employer failed to ensure the written operating procedures addressed the requirements for the safety systems and their functions. Identified safety systems and functions include but not limited to: a. High Discharge Pressure Shuts Down Compressors b. High Discharge Temperature Shuts Down Compressors c. High/Low Oil Pressure Differential Shuts Down Compressors d. High Accumulator Level Shuts Down Compressors e. Low Accumulator Level Shuts Down Pumps f. Ammonia Detector Alarms and Interlock Activation Of Ventilation System(s) g. Emergency Stops Outside of Entry to Engine Room Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation showing it is in compliance with the standard, including describing the steps it is taking to ensure written procedures address the requirements for the safety systems and their functions.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close