Violation Detail
Standard Cited: 19100106 D04 IV Flammable liquids.
Inspection Nr: 998042.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,080.00
Current Penalty: $2,156.00
Issuance Date: 03/18/2015
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 05/28/2015
Gravity: 10
Report ID: 0523900
Contest Date:
Final Order: 04/02/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/02/2015 | $2,156.00 | 05/28/2015 | Serious | |
Penalty | Z: Issued | 03/18/2015 | $3,080.00 | 05/28/2015 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.106(d)(4)(iv): 29 CFR 1910.106(d)(4)(iv): Ventilation. Every inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system; designed to provide for a complete change of air within the room at least six times per hour: (a) Dip Tank Paint Building, Flammable Storage Room; The ventilation system in place did not complete a change of air within the room at least six times per hour, in the inside storage room, containing approximately 30, 55 gallon drums, of flammable paint (flashpoints ranged from 95 F to 102 F) and other chemicals.