Violation Detail
Standard Cited: 19100304 F01 IV Wiring design and protection.
Inspection Nr: 907195.015
Citation: 01003
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $3,500.00
Current Penalty: $2,800.00
Issuance Date: 10/29/2013
Nr Instances: 2
Nr Exposed: 16
Related Event Code (REC):
Gravity: 5
Report ID: 0214700
Contest Date:
Final Order: 11/15/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/15/2013 | $2,800.00 | Serious | ||
Penalty | Z: Issued | 10/29/2013 | $3,500.00 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: a) Workplace, Ductwork Production Area- circuit breaker boxes on east wall, housing power to the production area including, but not limited to warehouse lights, press brake machines, plasma cutting machine and roll forming machine was blocked by an approximately 4'x7' Liner Cutter Machine; on or about 5/16/13. b) Workplace, Ductwork Production Area- circuit breaker box in center of production area housing power including, but not limited to warehouse lights and roll forming machines was blocked by a TDC Roll Former Machine; on or about 5/16/13. Note: Because abatement of this violation is already documented in the case file, the employer need not submit certification or documentation of abatement for this violation as normally required by CFR 1903.19.