Violation Detail
Standard Cited: 19100106 D04 I Flammable liquids.
This violation item has been deleted.
Inspection Nr: 893753.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,800.00
Current Penalty: $0.00
Issuance Date: 09/05/2013
Nr Instances: 1
Nr Exposed: 23
Abatement Date: 12/09/2013
Gravity: 10
Report ID: 0521400
Contest Date: 09/26/2013
Final Order: 10/23/2014
Related Event Code (REC): A
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 10/23/2014 | $0.00 | 12/09/2013 | Serious | |
Penalty | C: Contested | 11/18/2013 | $2,800.00 | 12/09/2013 | Serious | |
Penalty | Z: Issued | 09/05/2013 | $2,800.00 | 12/09/2013 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.106(d)(4)(i): "Construction." Openings to other rooms or buildings were not provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, or the floor in the storage area was not at least 4 inches below the surrounding floor. The room was not liquid-tight where the walls join the floor. A permissible alternate to the sill or ramp was not an open-grated trench inside of the room which drains to a safe location: On or about March 6, 2013, Fox Valley Systems, Inc., maintained an indoor storage room, known at the facility as the raw materials storage warehouse, where the employer stored flammable and combustible liquids. This room did not meet the requirements of an inside storage room for flammable liquids in that the openings to this room were not provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, nor was the floor, in the storage area at least 4 inches below the surrounding floor. Furthermore, there was not an open-grated trench inside of the room which drained to a safe location. DOCUMENTATION AND CERTIFICATION ARE REQUIRED FOR THIS ITEM.