Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
This violation item has been deleted.
Inspection Nr: 605598.015
Citation: 01003
Citation Type: Serious
Abatement Date: 04/11/2013
Initial Penalty: $1,700.00
Current Penalty: $0.00
Issuance Date: 01/10/2013
Nr Instances: 2
Nr Exposed: 6
Related Event Code (REC): C
Gravity: 5
Report ID: 0418100
Contest Date:
Final Order: 01/25/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/25/2013 | $0.00 | 04/11/2013 | Serious | |
Penalty | Z: Issued | 01/10/2013 | $1,700.00 | 04/11/2013 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of liquid that may be located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons of Class IB, IC, II, or III liquids in containers: a) Concrete Area-There was greater than 1700 gallons of Class I liquids outside of an inside storage room exposing employees to a fire hazard. Chemicals include, but are not limited to, resin, acetone, isopropyl alcohol, and S-2, on or about August 30, 2012. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).