Violation Detail
Standard Cited: 19100119 D03 IE Process safety management of highly hazardous chemicals.
Inspection Nr: 314198375
Citation: 01003
Citation Type: Serious
Abatement Status: X
Initial Penalty: $5,000.00
Current Penalty: $3,000.00
Issuance Date: 08/09/2010
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 09/23/2010
Gravity: 10
Report ID: 0418300
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
Substance: 0170
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/01/2010 | $3,000.00 | 09/23/2010 | Serious | |
| Penalty | Z: Issued | 08/09/2010 | $5,000.00 | 09/23/2010 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard: CHEMNEP
29 CFR 1910.119(d)(3)(i)(E): Process safety information pertaining to the equipment in the process did not include the ventilation system design requirements: a) On or about February 24, 2010 - the PSI did not contain information that was needed to ensure that the machine room ventilation air flow paths would prevent the accumulation of ammonia vapor in air at concentration greater than 16 percent. Additionally, the employer did not follow good engineering practice requirements for using non-manual, fail open air intake louvers and exhaust fans that were located in a manner that would promote air flow throughout the machine room and avoid short circuiting of ventilation air currents as specified in IIAR Bulletin 111-1991, Sections 5.1 and 5.2.