Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 313720757
Citation: 01003
Citation Type: Serious
Abatement Date: 01/28/2011 X
Initial Penalty: $7,000.00
Current Penalty: $7,000.00
Issuance Date: 01/05/2011
Nr Instances: 9
Nr Exposed: 10
Related Event Code (REC):
Gravity: 10
Report ID: 0830600
Contest Date:
Final Order:
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/27/2011 | $7,000.00 | 01/28/2011 | Serious | |
Penalty | Z: Issued | 01/05/2011 | $7,000.00 | 01/28/2011 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard: CHEMNEP
29 CFR 1910.119(d)(3)(ii): The employer did not document that the equipment in the process complied with Recognized And Generally Accepted Good Engineering Practices (RAGAGEP): a)The anhydrous ammonia lines that were located in Cellar 20, Basement, North Fan Room were not marked to identify the refrigerant in the lines. b)The anhydrous ammonia lines that were located in Cellar 20, Basement, North Fan Room were not marked to physical state of the refrigerant in the lines. c)The anhydrous ammonia lines that were located in Cellar 20, Basement, North Fan Room were not marked to indicate the relative pressure of the refrigerant in the lines. d)The anhydrous ammonia lines that were located in Cellar 20, Basement, North Fan Room were not marked to indicate direction of flow of the refrigerant in the lines. e)The ammonia receiver identified as C20-001 and located in Cellar 20, Basement, North Fan Room was not marked to indicate the system component type (RECEIVER). f)The ammonia receiver identified as C20-001 and located in Cellar 20, Basement, North Fan Room was not marked to indicate the system component pressure level designation. g)The drain pot located in Cellar 20, Basement, North Fan Room was not marked to indicate the system component type (DRAIN POT). h)The drain pot located in Cellar 20, Basement, North Fan Room was not marked to indicate the system component pressure level designation. i)The valves located in Cellar 20, Basement, North Fan Room were not all marked to indicate the system component type. Abatement Note: Abatement certification and documentation is required for this item (see enclosed "Sample Abatement-Certification Letter").