Violation Detail
Standard Cited: 19100119 D03 IB Process safety management of highly hazardous chemicals.
Inspection Nr: 313357089
Citation: 01003
Citation Type: Serious
Abatement Status: X
Initial Penalty: $7,000.00
Current Penalty: $6,000.00
Issuance Date: 03/28/2011
Nr Instances: 6
Nr Exposed: 460
Abatement Date: 08/31/2011
Gravity: 10
Report ID: 1032500
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | P: Petition to Mod Abatement | 08/02/2011 | $6,000.00 | 08/31/2011 | Serious | |
| Penalty | I: Informal Settlement | 04/18/2011 | $6,000.00 | 07/01/2011 | Serious | |
| Penalty | Z: Issued | 03/28/2011 | $7,000.00 | 05/02/2011 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard: CHEMNEP
29 CFR 1910.119(d)(3)(i)(B): Information pertaining to the equipment in the process did not include piping and instrument diagrams (P&ID's). a)In the vicinity of Compressor 2012: On or about October 4, 2010 and at times prior thereto, the P&ID did not represent valves, and pipe sizes were labeled improperly. b)In the vicinity of Compressor 2002: On or about October 4, 2010 and at times prior thereto, the P&ID did not represent a pipe with valves, pipe sizes were labeled improperly, and valves were missing or drawn in the wrong places. c)In the vicinity of Compressor 2009: On or about October 4, 2010 and at times prior thereto, the P&ID did not represent a pipe with valves, pipe sizes were labeled improperly, and valves were missing or drawn in the wrong places. d)In the vicinity of the High Pressure Receiver: On or about October 4, 2010 and at times prior thereto, the P&ID represented pipes and valves that did not exist. e)In the vicinity of the ammonia diffusion system: On or about October 4, 2010 and at times prior thereto, the P&ID did not label or show the origination of a pipe. f)In the vicinity of the dehumidify vessel: On or about October 4, 2010 and at times prior thereto, the P&ID did not accurately represent valves and piping. Note: Abatement certification and supporting documentation are required for this item.