Violation Detail
Standard Cited: 19100159 C02 Automatic sprinkler systems.
Inspection Nr: 1873666.015
Citation: 01003
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/31/2026
Nr Instances: 2
Nr Exposed: 80
Abatement Date: 06/30/2026
Gravity: 1
Report ID: 0936100
Contest Date:
Final Order: 04/24/2026
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 03/31/2026 | $0.00 | 06/30/2026 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.159(c)(2): The employer shall properly maintain an automatic sprinkler system installed to comply with this section. The employer shall assure that a main drain flow test is performed on each system annually. The inspector's test valve shall be opened at least every two years to assure that the sprinkler system operates properly. On or about February 09, 2026, and at times prior thereto, the employer did not properly maintain or inspect the installed automatic sprinkler system. This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) HQ building b) ATCC building