Violation Detail
Standard Cited: 19100305 J04 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1812629.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,384.00
Current Penalty: $3,195.00
Issuance Date: 06/04/2025
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 06/30/2025
Gravity: 1
Report ID: 0419400
Contest Date:
Final Order: 07/02/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/02/2025 | $3,195.00 | 06/30/2025 | Serious | |
| Penalty | Z: Issued | 06/04/2025 | $6,384.00 | 06/30/2025 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.305(j)(4)(ii): As it applies to motors, motor circuits and controllers; a disconnecting means for the controller was not located within sight of the controller location ( i.e. that one piece of equipment shall be within sight of another piece of equipment, the piece of equipment shall be visible and not more than 50 feet from the other). (a) North Outside press break - On or about March 21, 2025, the employees operate a 300-ton full revolution press break that has the motor disconnect located inside the building out of sight, exposing employees to caught in hazards.