Violation Detail
Standard Cited: 19100107 B09 Spray finishing using flammable and combustible materials.
Inspection Nr: 1783140.015
Citation: 01003
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,839.00
Current Penalty: $2,903.40
Issuance Date: 12/27/2024
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 01/28/2025
Gravity: 1
Report ID: 0521100
Contest Date:
Final Order: 01/21/2025
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/21/2025 | $2,903.40 | 01/28/2025 | Serious | |
Penalty | Z: Issued | 12/27/2024 | $4,839.00 | 01/28/2025 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.107(b)(9): Spray booths shall be so installed that all portions are readily accessible for cleaning. A clear space of not less than 3 feet on all sides shall be kept free from storage or combustible construction: On or about October 24, 2024, at a facility located at 6610 Wisconsin 44 in Pickett, WI; storage along the outside west wall of the spray booth in Bay 2 did not allow for a clear space of 3 feet on all sides. Cardboard boxes of PPE, spray booth filters, and winter jackets were stored along the outer west wall of the spray booth.